YASKAWA Z1000 User Manual page 140

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

4.7 Basic Drive Setup Adjustments
n
L5-01: Number of Auto Restart Attempts
Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,
the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
No.
L5-01
n
L5-03: Time to Continue Making Fault Restarts (enabled only when L5-05 = 0)
Although the drive will continue to execute fault restarts, this parameter will cause a fault if a fault restart cannot occur after
the time set to L5-03 passes.
All major faults will cause the drive to stop. For some faults it is possible to configure the drive to attempt a restart automatically.
After the fault occurs, the drive baseblocks for L2-03 seconds. After the baseblock is removed, the drive checks if a fault
condition still exists. If no fault condition exists, the drive will attempt to restart the motor. If the restart is successful, the drive
performs a Speed Search (Regardless of the status of b3-01 "Speed Search Selection") from the set speed command and the
Auto Restart Attempts count is increased by one. Even if the restart fails, the restart count is increased by one as long as the
drive attempted to rotate the motor. The restart count will not be incremented if the restart is not attempted due to a continuing
fault condition, (i.e., an ov fault). The drive waits L5-03 seconds before attempting another restart.
No.
L5-03
The auto restart count is reset back to 0 if any of the following occur:
• No further faults for 10 minutes after the last retry.
• The drive power is turned off (the drive must be without power long enough to let control power dissipate).
• The RESET key is pushed after the last reset attempt.
The setting of parameter L5-02 determines whether the fault output (MA-MB) will be closed during an auto restart attempt.
The setting of L5-02 can be important when using the drive with other equipment.
The following faults will allow the Auto Restart function to initiate:
• oC (Overcurrent)
• LF (Output Phase Loss)
140
Name
Number of Auto Restart Attempts
Name
Time to Continue Making Fault Restarts
Run
ov
Fault
trying each
L5-03 seconds successful
Attempts
L2-03
L5-01
Count
Voltage
remains high
for a long time,
then reset (1)
Figure 4.25 Automatic Restart Timing Diagram
oC
oC
try, but
failed
successful
L2-03
L2-03
1
2
3
Drive trips on oC,
oC condition
resets (2) and tries
gone, resets (3)
again but motor still
and runs.
shorted, trips again.
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Setting Range
0 to 10 Times
Setting Range
0.00 to 600.0 s
Time
Default
0 Times
Default
180.0 s