Item
Undervoltage Protection
Protection
Momentary Power Loss
Functions
Ride-Thru
Heatsink Overheat
Protection
Stall Prevention
Ground Protection
DC Bus Charge LED
Area of Use
Ambient Temperature
Environment
Humidity
Storage Temperature
Altitude
Vibration/Shock
Standards
Protection Design
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<2> Overload protection may be triggered when operating with 100% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.
<4> A 24 V power supply Unit (Model Nos. PS-A10LB, PS-A10HB) is required for models 2A0011 to 2A0059 and 4A0005 to 4A0052 if the application
must continue running for up to 2 seconds during a momentary power loss.
<5> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
<6> Setting L8-09 to 1 enables ground fault detection in models 2A0075 to 2A0396, 4A0052ooA, and 4A0065 to 4A0590.
<7> Drive models 2A0011 to 2A0273 and 4A0011 to 4A0302 are designed to IP20 NEMA 1, UL Type 1 specifications with a protective cover on the
top. Removing this top protective cover voids the NEMA 1, UL Type 1 protection while maintaining IP20 conformity; removing the bottom conduit
bracket voids the NEMA 1,UL Type 1 protection and IP20 conformity.
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
200 V class: Stops when DC bus voltage falls below approx. 190 V
400 V class:
Stops when DC bus voltage falls below approximately 350 V when using an input voltage lower than 400V
Stops when DC bus voltage falls below approximately 380 V when using an input voltage lower than 460
V
Stops when DC bus voltage falls below approximately 440 V when using an input voltage of 460 V or
higher
Immediately stop after 15 ms or longer power loss
Continuous operation during power loss shorter than 2 s by speed search function
Thermistor
Stall Prevention is available during acceleration, deceleration, and during run.
<5> <6>
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
-10 °C to +40 °C (14 °F to 104 °F) IP20 NEMA 1, UL Type 1 Enclosure, External Heatsink (2A0011 to
2A0273 and 4A0005 to 4A0302)
-10 °C to +50 °C (14 °F to 122 °F) IP00/Open Type Enclosure (2A0343 and 2A0396, and 4A0361 to
4A0590)
Note:
1. To install a heatsink on the outside of a panel, design the panel to keep the air temperature
inside the panel within 10 °C (18 °F) [5 °C (9 °F) for 2A0273 and 4A0124] of the outside
air temperature.
2. Ambient temperature range for continuous operations is -10 °C to +40 °C (14 °F to 104
°F) when external heatsink installation method is applied for models 2A0343 and
2A0396 and 4A0361 to 4A0590.
95% RH or less (no condensation)
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
Altitude Derating on page 280
for details.
2
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
(2A0011 to 2A0031 and 4A0005 to 4A0027) or
2
2.0 m/s
(2A0046 to 2A0396 and 4A0034 to 4A0590)
IEC/EN 61800-5-1
IP00/Open Type enclosure, IP20 NEMA 1, UL Type 1 enclosure
A.2 Drive Specifications
Specification
<3>
<7>
<4>
Refer to
A
275