YASKAWA Z1000 User Manual page 218

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

5.4 Fault Detection
HOA Keypad Display
The HOA keypad battery is low or the battery has
been replaced
An error has occurred in the Real-Time Clock
function of the HOA keypad
HOA Keypad Display
UL3
Cause
Parameter settings are not appropriate for the load Check the settings of parameters L6-02 and L6-03.
There is a fault on the machine side
HOA Keypad Display
UL6
Cause
The output current has fallen below the motor
underload curve defined in L6-14 for longer than
the time set to L6-03
HOA Keypad Display
Uv1
Cause
Input power phase loss
One of the drive input power wiring terminals is
loose
There is a problem with the voltage from the drive
input power
The power has been interrupted
The main circuit capacitors are worn
The relay or contactor on the soft-charge bypass
circuit is damaged
HOA Keypad Display
Uv2
Cause
Internal circuitry is damaged
218
Replace the HOA keypad battery and set the Real-Time Clock.
Replace the HOA keypad. For instructions on replacing the HOA keypad, contact Yaskawa or your
nearest sales representative.
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the
allowable time (L6-03).
Check the load for any problems.
Motor Underload
The weight of the load has fallen below the underload curve defined in L6-14.
Adjust the value set to L6-14 so that output current remains above the motor underload curve during
normal operation.
DC Bus Undervoltage
Voltage in the DC bus fell below the undervoltage detection level (L2-05).
• For 200 V class drives: approximately 190 V
• For 400 V class drives: approximately 440 when using input voltages 460 V or higher (350 V when
E1-01 is less than 400, and 380 V when 400V ≤ E1-01 < 460 V )
The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set
to L2-05 for longer than the time set to L2-02.
• The main circuit drive input power is wired incorrectly.
• Correct the wiring.
• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.
and Tightening Torque on page 83
• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main
circuit magnetic contactor.
Correct the drive input power.
• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.
• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Fault Name
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
for details.
Fault Name
Possible Solution
Refer to Wire Gauges

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents