YASKAWA Z1000 User Manual page 132

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

4.7 Basic Drive Setup Adjustments
n
C1-01 to C1-04: Accel, Decel Times 1 and 2
Four different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched
automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).
Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02
are the default active accel/decel settings.
No.
C1-01
C1-02
C1-03
C1-04
Switching Acceleration Times by Digital Input
Accel/decel time 1 is active by default if no input is set.
Accel/Decel Time Sel. 1
H1-oo = 7
0
1
Figure 4.18
shows an operation example for changing accel/decel. times. The example below requires that the stopping method
be set for "Ramp to stop" (b1-03 = 0).
Switching Accel/Decel Times by a Frequency Level
The drive can switch between different acceleration and deceleration times automatically. The drive will switch from accel/
decel time 2 in C1-03 and C1-04 to the default accel/decel time in C1-01 and C1-02 when the output frequency exceeds the
frequency level set in parameter C1-11. When the frequency falls below this level, the accel/decel times are switched back.
Figure 4.19
shows an operation example.
Note:
Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by the frequency level set to C1-11.
For example, if accel/decel time 2 is selected, the drive will use only accel/decel time 2; it will not switch from accel/decel time 2 to the
selected time.
132
Parameter Name
Acceleration Time 1
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Table 4.17 Accel/Decel Time Selection by Digital Input
Decel Time 1
(C1-02)
Accel Time 1
(C1-01)
Output
frequency
ON
FWD (REV)
Run command
Accel/Decel Time Selection 1
(Terminals S1 to S7, H1- oo = "7")
Figure 4.18 Timing Diagram of Accel/Decel Time Change
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Setting Range
0.1 to 6000.0 s
Active Times
Acceleration
C1-01
C1-03
Decel Time 2
(C1-04)
Accel Time 2
(C1-03)
Decel Time 1
(C1-02)
ON
OFF
ON
Default
30.0 s
Deceleration
C1-02
C1-04

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents