B.8 L: Protection Function
B.8 L: Protection Function
L parameters provide protection to the drive and motor, including control during momentary power loss, stall prevention,
frequency detection, fault restarts, overtorque and undertorque detection, and other types of hardware protection.
u

L1: Motor Protection

No.
(Addr.
Name
Hex)
L1-01
Motor Overload
(480)
Protection Selection
L1-02
Motor Overload
(481)
Protection Time
Motor Overheat Alarm
L1-03
Operation Selection
(482)
(PTC input)
Motor Overheat Fault
L1-04
Operation Selection
(483)
(PTC input)
Motor Temperature
L1-05
Input Filter Time (PTC
(484)
input)
L1-08
(1103)
oL1 Current Level
<2>
Continuous
L1-13
Electrothermal
(46D)
Operation Selection
<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Available in drive software versions PRG: 1016 and later.
<3> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<4> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for
a maximum applicable motor capacity up to and including 11 kW, 2A0031, 4A0021 (input voltage 460 V or higher) or 4A0027 (input voltage lower
than 460 V) and one decimal place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW, 2A0046, 4A0027 (input voltage 460
V or higher) or 4A0034 (input voltage lower than 460 V) .
312
LCD Display
0: Disabled
Mtr OL Charact
1: General purpose motor (standard fan cooled)
0: OL1 Disabled
4: PM motor with variable torque control
1: VT Motor
The drive may not be able to provide protection when using
4: PM Motor
multiple motors, even if overload is enabled in L1-01. Set L1-01
to 0 and install separate thermal relays to each motor.
Sets the motor thermal overload protection (oL1) time.
MOL Time Const
Sets operation when the motor temperature analog input
Mtr OH Alarm Sel
(H3-02 or H3-10 = E) exceeds the alarm level.
0 : Ramp to Stop
0: Ramp to stop
1: Coast to Stop
1: Coast to stop
2: Fast-Stop
2: Fast Stop (decelerate to stop using the deceleration time in
3: Alarm only
C1-09)
3: Alarm only ("oH3" will flash)
Sets stopping method when the motor temperature analog input
Mtr OH Fault Sel
(H3-02, or H3-10 = E) exceeds the oH4 fault level.
0 : Ramp to Stop
0: Ramp to stop
1: Coast to Stop
1: Coast to stop
2: Fast-Stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
Adjusts the filter for the motor temperature analog input
Mtr Temp Filter
(H3-02, or H3-10 = E).
Sets the reference current for motor thermal overload detection
oL1 Current Lvl
for the motor in amperes.
Mtr OL Mem Sel
0: Disabled
0: Disabled
1: Enabled
1: Enabled
2: Enable using Real Time Clock
2: Enabled(RTC)
Description
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Values
Page
<1>
Default:
Range: 0, 1, 4
Default: 1.0 min
Min.: 1.0
Max.: 5.0
Default: 3
Range: 0 to 3
Default: 1
Range: 0 to 2
Default: 0.20 s
Min.: 0.00
Max.: 10.00
<3>
Default:
Min.: 10% of
drive rated
current
Max.: 150% of
drive rated
<4>
current
Default: 1
Range: 0 to 2