4.13 Advanced Drive Setup Adjustments
No.
o2-04
n
A1-06: Application Preset
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters
to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
n
b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
b1-04
Setting 0: Reverse Enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse Disabled
Drive disregards a Reverse run command or a negative frequency reference.
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
b1-14
Setting 0: Standard
Setting 1: Switch Phase Order
The direction of the motor is reversed.
n
b1-17: Run Command at Power Up
Determines whether an external Run command that is active during power up will start the drive.
No.
b1-17
Setting 0: Disregarded
A new Run command must be issued after power up. Cycle the Run command to start the drive.
Setting 1: Allowed
The motor will start immediately after a power up if a Run command is already enabled.
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin
rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to
powering up the drive. Failure to comply may cause serious injury.
n
b2-01: DC Injection Braking Start Frequency
Active when "Ramp to Stop" is selected as the stopping method (b1-03 = 0).
No.
b2-01
The function triggered by parameter b2-01 depends on the control mode that has been selected.
158
Parameter Name
Reverse Operation Selection
Parameter Name
Phase Order Selection
Parameter Name
Run Command at Power Up
Name
DC Injection Braking Start Frequency
Parameter Name
Drive Model Selection
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Setting Range
Determined by
0.0 to 10.0 Hz
Default
1
Default
0
Default
1
Default
A1-02