4.13 Advanced Drive Setup Adjustments
No.
o1-02
Setting 1: Frequency Reference (U1-01)
Setting 2: Motor Direction
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Monitor
The monitor value selected by o1-01 will be displayed.
n
o1-03: HOA Keypad Display Selection
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before setting
parameters o1-10 and o1-11.
No.
o1-03
Setting 0: 0.01 Hz Units
Setting 1: 0.01% Units (100% = Max Output Frequency)
Setting 2: r/min Units (Calculated by the Max Output Frequency and the Number of Motor Poles)
Setting 3: User-set Units (Use o1-10, o1-11)
Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to
o1-11.
For example, to have the maximum output frequency displayed as "100.00", set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with
2 decimal points).
Note:
1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
U1-01: frequency reference
U1-02: output frequency
U1-16: output frequency after softstarter (accel/decel ramp generator)
d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires entering the number of motor poles to E2-04 and E5-04.
n
o1-06: User Monitor Selection Mode
Normally the monitors shown directly below the active monitor are the next two sequential monitors. If o1-06 (User Monitor
Selection Mode) is set to 1: "3 Mon Selectable", those two monitors are locked as specified by parameters o1-07 and o1-08
and will not change as the top parameter is scrolled with the Up/Down Arrow keys.
No.
o1-06
Setting 0: 3 Monitor Sequential (Displays the Next 2 Sequential Monitors)
Setting 1: 3 Monitor Selectable (o1-07, and o1-08 Selected Monitor Is Shown)
n
o1-07: Second Line Monitor Selection
Selects which monitor will be displayed in the second line. The monitor parameter number is entered into the spaces provided:
Uo-oo.
For example, set "403" to display monitor parameter U4-03.
No.
o1-07
n
o1-08: Third Line Monitor Selection
Selects which monitor will be displayed in the third line. The monitor parameter number is entered into the spaces provided:
Uo-oo.
For example, set "403" to display monitor parameter U4-03.
No.
o1-08
188
Name
User Monitor Selection after Power Up
Name
HOA Keypad Display Selection
Name
User Monitor Selection Mode
Name
Second Line Monitor Selection
Name
Third Line Monitor Selection
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Setting Range
1 to 5
Setting Range
0 to 3
Setting Range
0, 1
Setting Range
101 to 699
Setting Range
101 to 699
Default
1
Default
0
Default
0
Default
102
Default
103