Backup/Restoration; Backup/Restoration Setting - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3.4

Backup/Restoration

3.4.1

Backup/restoration setting

The storage location for backup data can be set.
For how to use the backup/restoration, refer to the following.
Set the following items with touching the items on the GOT.
Item
The drive for storing backup settings, including parameters and passwords for
Drive for backup setting
controllers, can be selected.
Drive for backup data
The drive for storing backup data can be selected.
The GOT automatically backs up data when triggers (Rise, Time) specified for
Trigger backup setting
each backup setting are met.
Set the maximum number of backup data to be stored.
Max. of backup data
(When 0 is specified, the GOT does not check the number of backup data to be
stored.)
Set whether to specify the CPU No. at a backup.
(When [YES] is selected, the GOT starts to communicate with only the
Enable CPU No. setting
specified PLC. Therefore the network batch backup/restoration on the multiple
PLCs cannot be executed.)
Retain file register inf.
Set whether to retain the file register information at a restoration.
during restor
3 - 10
3.4 Backup/Restoration
GOT2000 Series User's Manual (Monitor)
Description
Setting range
A: Built-in SD card
B: USB Drive
E: USB Drive
F: USB Drive
G: USB Drive
X: Drive
<Default: X: Drive>
A: Built-in SD card
B: USB Drive
E: USB Drive
F: USB Drive
G: USB Drive
X: Drive
<Default: X: Drive>
None/Rise/Time
<Default: None>
3.5 Trigger Backup
Setting range: 0 to 50
<Default: 0>
YES/NO
<Default: NO>
YES/NO
<Default: NO>