Step 5.
When the screen shown below appears, the changed communication set value of the FX3U-ENET-ADP is
written normally to the CPU.
For making valid the contents of setting, turn OFF the power of the CPU, and then turn it ON again. Change
the setting of the subnet mask pattern and default router IP address using the same procedure if necessary.
An error message appears in the following cases. Touch the
the setting procedure again.
• When the CPU is running
The following error message appears. Stop the running status of the CPU.
• When a communication error occurs
Set the communication between the GOT and the CPU to the normal status.
• When the memory cassette is write-protected
Set to OFF the write-protect switch of the memory cassette.
• When writing to the CPU is protected by the keyword
Clear the protection by the keyword against writing.
16 - 44
16.3 FX3U-ENET-ADP Communication Setting Function