Mitsubishi Electric GOT2000 Series User Manual page 375

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Error
Error message
code
Same sta. on GOT & project data.
424
Review communication parameter.
A duplicate IP address has been
425
detected.
Confirm the setting.
Wireless LAN unit is not mounted or
430
a hardware error occurred.
Connectable access point is not
431
found.
Wireless LAN connection settings
432
are not specified.
Failed to authenticate the access
433
point.
GOT hardware version not supported
434
by wireless LAN connection
The label information has been
440
updated.
The specified CPU is updating the
441
label information.
Resolving the label information.
442
Do not turn off the power during the
process.
PLC cannot handle as requested.
448
Correct devices.
Dedicated device is out of range.
449
Confirm device range.
Path has changed or timeout
450
occurred in redundant system.
MELSEC redundant system settings
451
and current config. do not match.
System (A/B) and system status
452
(control/standby) not determined in
redundant system.
The standby system is set in a
453
system other than the MELSEC iQ-R
redundant system.
460
Communication unit error
The station number set in the GOT's utility is the same as the station number set in
the Ethernet setting of GT Designer3 (the station number of the PLC side Ethernet
module) or in the project data.
Check the following contents so that the multiple station numbers should not be the
same.
• Check the GOT's station number in the GOT's utility.
• Check the station number set in the project data.
• Check the station number set in the Ethernet setting.
(Set the station number so that it becomes the same as the station number of
the PLC side Ethernet module set in the parameter setting of GX Developer.)
• When using the station No. switching function, check the data of the switching
station No. device.
The GOT has the same IP address as another device.
Change the IP address of the GOT or the device.
The wireless LAN communication unit is not installed on the side interface.
Check that the unit is installed properly.
Check the setting for an accessible access point, and the wireless LAN connection
setting.
After configuring the wireless LAN connection setting, enable the wireless LAN
connection function.
GT Designer3 (GOT2000) Screen Design Manual
Check if the authentication method specified in the wireless LAN connection
setting is the same as that on the access point side.
Use a GOT with hardware version B or later.
For how to check the hardware version, refer to the following.
GOT2000 Series User's Manual (Hardware)
The label name resolution will be executed automatically.
Wait for the completion.
The global label information of the specified CPU will be updated.
Wait for the completion.
The label name resolution is being executed.
Wait for the completion.
A device outside the range of PLC CPU file registers and the buffer memory was
specified.
Correct the monitor device by setting file register of the PLC CPU.
• Set the address for the special function module in the GOT monitor available
range.
• Set the device in the GOT monitor available range.
The path has been switched or timeout occurred in the redundant system.
• Check the PLC CPU to know if the path has been switched.
• Check the cable connection status, the communication unit installation status,
and the PLC CPU status.
• This error may occur when the load of the PLC CPU becomes heavier when
accessing other stations. In such a case, transfer the data of the other stations to
the host station PLC CPU and monitor them at the host.
• Perform one of the following operations if the PLC scanning time is long: COM
instruction/Extension of END processing/Setting of the number of processing
times for general data/Data update batch processing.
Change the MELSEC redundant setting in accordance with the actual MELSEC
redundant system.
• Set one system as system A or control system and the other system as system
B or standby system.
• Do not specify any connection destination system (request destination module I/
O number).
• When the MELSEC redundant setting is not configured, delete the specified
device of the standby system.
• Configure the redundant system using the MELSEC iQ-R series.
• Reset the power of the GOT.
• Replace the unit.
8.2 Error Codes and System Alarm List
Action
Channel
No. storage
8
8 - 9