■3. System alarm list
The system alarm detected with GOT is shown below.
Error
Error message
code
Project data contains unsupported
300
objects.
Project data contains unsupported
301
functions.
Project data contains unsupported
302
settings.
Set monitor points too large.
303
Decrease setting points.
Background loading of the system
305
package failed.
No project data. Download screen
306
data.
307
Monitor device not set
No comment data. Download
308
comment.
309
Device reading error. Correct device.
Project data does not exist or out of
310
range.
No. of alarm has exceeded upper
311
limit. Delete restored alarm.
No. of sampling has exceeded upper
312
limit. Delete collected data.
315
Device writing error. Correct device.
Cannot display or input operation
316
value. Review expression.
Classification code
33h
70h
[RKC SR Mini HG(MODBUS)]
90h
[IAI ROBO CYLINDER]
34h
91h
[IAI X-SEL]
30h
[Panasonic MINAS-A4]
27h
31h
[Panasonic MINAS-A5]
E0h
[MODBUS/RTU]
E1h
[Computer]
25h
[PROFIBUS DP]
20h
26h
[DeviceNet]
F0h
[MODBUS/TCP,Gateway]
F1h
[Computer]
F2h
[Ethernet(SLMP), Gateway]
Install the latest version of GT Designer3 and write the package data again to the
GOT.
Install the latest version of GT Designer3 and write the package data again to the
GOT.
Install the latest version of GT Designer3 and write the package data again to the
GOT.
Decrease the number of objects from the displayed screen. For the number of
maximum objects for 1 screen, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual
Check that the data storage, which stores the package data and GOT project data,
is installed and the data is not damaged.
The project data is not downloaded or the screen data is not sufficient.
Download the project data or screen data.
The monitor device of the object is not set.
Set the monitor device of the object.
The comment file does not exist.
Create the comment file and download to GOT.
The error occurred when reading a continuous device.
Correct the device.
Specified base screen / window screen does not exist in the project data.
Specified base screen / window screen is out of the permissible area. Specify the
existing base screen / window screen.
The number of alarm histories that can be observed by the alarm history display
function has exceeded the maximum points.
Delete the restored history to decrease the number of alarm histories.
The collection frequency exceeded the upper limit when "Store Memory" and
"Accumulate/Average" were set in the scatter graph.
Approve "Clear trigger" setup in the scatter graph.
Set the "Operation at frequency over time" to "Initialize and Continue" in scatter
graph.
Error occurred while writing in the device.
Correct the device.
In indirect specification of comment/parts number, the data operation result
exceeded the range in which device type can be expressed.
Review the data operational expression, in order not exceeding the range in which
the device type can be expressed.
Description
Action
8.2 Error Codes and System Alarm List
Channel
No. storage
8
8 - 5