TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI3_GAS_PRESSURE_ALARM
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
X110_BI4_CB_SPRING_CHARGED
GUID-3C981DB3-EFC0-490C-AE96-2C5B16CC7E00 V1 EN
Figure 82:
Circuit breaker close enable logic
The configuration includes logic for generating circuit breaker external closing and
opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect additional signals for opening and closing of circuit breaker
in local or remote mode, if applicable for the configuration.
CONTROL_LOCAL
FALSE
CONTROL_REMOTE
FALSE
GUID-73713DC3-F7C8-4821-AF9D-2A7568AFE963 V1 EN
Figure 83:
External opening command for circuit breaker
B1
CONTROL_LOCAL
B2
FALSE
B1
CONTROL_REMOTE
B2
FALSE
GUID-5BED9700-F389-4A3E-AE41-6854954D5819 V1 EN
Figure 84:
External closing command for circuit breaker

Functional diagrams for measurement functions

The phase current inputs to the IED are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card in
the back panel. Similarly, sequence current measurement CSMSQI1 measures the
sequence current and the residual current measurement RESCMMXU1 measures the
residual current.
REF615 standard configurations
NOT
IN
OUT
NOT
IN
OUT
NOT
IN
OUT
AND
B1
O
B2
B1
B2
AND
B1
O
B2
AND
O
B1
B2
AND
O
Section 3
AND6
B1
O
CBXCBR1_ENA_CLOSE
B2
B3
B4
B5
B6
OR
O
CBXBCR1_AU_OPEN
OR
O
CBXCBR1_AU_CLOSE
91