Default Disturbance Recorder Settings - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
3.5.2.2
REF615
Application Manual
Table 21:
Default connections for binary inputs
Binary input
Description
X120-BI1
Blocking of overcurrent instantaneous stage
X120-BI2
Circuit breaker closed indication
X120-BI3
Circuit breaker open indication
X120-BI4
Reset of master trip lockout
Table 22:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Circuit breaker failure protection trip to upstream breaker
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2
X100-SO1
General start indication
X100-SO2
General operate indication
Table 23:
Default connections for LEDs
LED
Description
1
Non-directional overcurrent operate
2
Non-directional earth-fault operate
3
Sensitive earth-fault operate
4
Negative sequence overcurrent or phase discontinuity operate
5
Thermal overload alarm
6
Breaker failure operate
7
Disturbance recorder triggered
8
-
9
Trip circuit supervision alarm
10
Arc protection operate
11
Autoreclose in progress

Default disturbance recorder settings

Table 24:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
Table continues on next page
REF615 standard configurations
Section 3
99