Default Disturbance Recorder Settings - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
3.14.2.2
REF615
Application Manual
LED
Description
9
Trip circuit supervision alarm
10
Arc protection operate
11
Autoreclose in progress

Default disturbance recorder settings

Table 69:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
5
-
6
-
7
-
8
-
9
-
10
-
11
-
12
-
Table 70:
Default disturbance recorder binary channels
Channel
ID text
1
PHLPTOC1 - start
2
PHHPTOC1 - start
3
PHLPTOC2 - start
4
PHIPTOC1 - start
5
NSPTOC1 - start
6
NSPTOC2 - start
7
EFLPTOC1 - start
8
EFHPTOC1 - start
9
EFIPTOC1 - start
10
EFLPTOC2 - start
11
-
12
PDNSPTOC1 - start
13
T1PTTR1 - start
14
CCBRBRF1 - trret
15
CCBRBRF1 - trbu
Table continues on next page
REF615 standard configurations
Section 3
Level trigger mode
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
Positive or Rising
-
Positive or Rising
Positive or Rising
Level trigger off
Level trigger off
357

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents