ABB relion REF615 Applications Manual page 252

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
246
X110_BI4_CB_SPRING_CHARGED
GUID-2E6D31BF-26F4-47CF-8E05-295BB466E4AD V1 EN
Figure 355:
Logic for start of circuit-breaker spring charging
Two separate trip circuit supervision functions are included: TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. Both functions are
blocked by the master trip TRPPTRC1 and TRPPTRC2 and the circuit breaker open
signal.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR1_ALARM
TCSSCBR2_ALARM
GUID-F5BCA344-DDE2-4504-91E7-B5A0EB19A8A3 V1 EN
Figure 356:
Trip circuit supervision function
NOT
IN
OUT
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
O
B2
1MRS756378 S
CB_SPRING_DISCHARGED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR_ALARM
REF615
Application Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents