Functional Diagrams For Protection - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.13.3.1
328
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.

Functional diagrams for protection

The functional diagrams describe the IED's protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection. Three
of them include directional functionality DPHxPDOC.
GUID-BD8968B4-3161-4D6F-9B9D-FD51C828C872 V1 EN
Figure 505:
Overcurrent protection function
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC2_OPERATE
GUID-2AC404B1-6335-45C6-B65A-549C6348C40E V1 EN
Figure 506:
Directional overcurrent protection functions
The upstream blocking from the start of the second low stage of three-phase
directional overcurrent protection DPHLPDOC2 is connected to the binary output.
PHIPTOC1
BLOCK
OPERATE
ENA_MULT
START
DPHHPDOC1
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC1
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC2
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
OR6
B1
O
B2
B3
B4
B5
B6
1MRS756378 S
PHIPTOC1_OPERATE
PHIPTOC1_START
DPHHPDOC1_OPERATE
DPHHPDOC1_START
DPHLPDOC1_OPERATE
DPHLPDOC1_START
DPHLPDOC2_OPERATE
DPHLPDOC2_START
DPHxPDOC_OPERATE
REF615
Application Manual