Functional Diagrams - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
3.12.3
REF615
Application Manual
Channel
ID text
41
X130BI1 - ext OC blocking
42
X130BI2 - CB closed
43
X130BI3 - CB opened
44
SECRSYN1 - sync inpro
45
SECRSYN1 - sync ok
46
SECRSYN1 - cl fail al
47
SECRSYN1 - cmd fail al
48
ARCSARC1 - ARC flt det
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
49
ARCSARC1 - operate
50
ARCSARC2 - operate
51
ARCSARC3 - operate
52
DARREC1 - inpro
53
DARREC1 - close CB
54
DARREC1 - unsuc recl

Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED's standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder's parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
The phase voltages to the IED are fed from a voltage transformer. The residual voltage
to the IED is fed from either residually connected VTs, an open delta connected VT
or internally calculated.
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.
REF615 standard configurations
Section 3
Level trigger mode
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Positive or Rising
Positive or Rising
Positive or Rising
Level trigger off
Level trigger off
Level trigger off