ABB relion REF615 Applications Manual page 225

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
REF615
Application Manual
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-63DB00F4-441B-4B7E-8F02-500921B8C9C6 V1 EN
Figure 313:
Signals for opening coil of circuit breaker 1
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI3_GAS_PRESSURE_ALARM
GUID-B74256B7-3CF6-464D-A6BB-90B83D2732E9 V1 EN
Figure 314:
Circuit breaker 1 close enable logic
Connect the higher-priority conditions before enabling the closing of
circuit breaker. These conditions cannot be bypassed using bypass
feature of the function.
T1PTTR1_BLK_CLOSE
GUID-3E75311B-A42A-4A5D-9122-D93FBD773BB3 V1 EN
Figure 315:
Circuit breaker 1 close blocking logic
The configuration includes the logic for generating circuit breaker external closing
and opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect additional signals for opening and closing of circuit breaker
in local or remote mode, if applicable for the configuration.
REF615 standard configurations
OR6
B1
B2
B3
B4
B5
B6
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
X110_BI4_CB_SPRING_CHARGED
NOT
IN
OUT
NOT
IN
OUT
NOT
IN
OUT
OR6
B1
B2
B3
B4
B5
B6
Section 3
O
CB_OPEN_COMMAND
AND6
B1
O
CBXCBR1_ENA_CLOSE
B2
B3
B4
B5
B6
O
CBXCBR1_BLK_CLOSE
219