1MRS756378 S
REF615
Application Manual
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
TRUE
CBXCBR1_ENA_CLOSE
FALSE
CBXCBR1_BLK_CLOSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
GUID-38527A0A-7F5E-4C8B-8155-2544FA45C4ED V2 EN
Figure 478:
Circuit breaker control logic: Circuit breaker 1
Connect the addition signals required by the application for closing
and opening coil of circuit breaker.
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-84F9FA17-9CAC-4B05-9BBB-041DCB249220 V1 EN
Figure 479:
Circuit breaker control logic: Signals for closing coil of circuit breaker
1
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
EFLPTOC2_OPERATE
GUID-C5BCF098-8F91-4484-B7C4-C737DF86A0B3 V1 EN
Figure 480:
Circuit breaker control logic: Signals for opening coil of circuit breaker
1
Connect higher-priority conditions before enabling the closing of
circuit breaker. These conditions cannot be bypassed using bypass
feature of the function.
REF615 standard configurations
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
OR
B1
O
B2
OR6
B1
O
B2
B3
B4
B5
B6
Section 3
CBXCBR1_SELECTED
CBXCBR1_EXE_OP
CBXCBR1_EXE_CL
CB_CLOSE_COMMAND
CB_OPEN_COMMAND
313