ABB relion REF615 Applications Manual page 351

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
REF615
Application Manual
X110_BI5_CB_TRUCK_IN_TEST
X110_BI6_CB_TRUCK_IN_SERVICE
CBXCBR1_OPENPOS
ESSXSWI1_OPENPOS
GUID-142CE220-F290-41CB-9E39-1B7080026BEB V1 EN
Figure 537:
Disconnector interlocking logic
Connect the additional signals for the application for closing of
earthing switch.
X110_BI7_ES1_OPENED
X110_BI8_ES1_CLOSED
X110_BI1_PLUG_OUT
X110_BI5_CB_TRUCK_IN_TEST
GUID-C582C1A4-2E92-40E3-A812-CC44D1A1FE46 V1 EN
Figure 538:
Earthing switch close enable logic
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earth-switch position status, status of the trip logics,
gas pressure alarm and circuit-breaker spring charging status.
The OKPOS output from DCSXSWI defines whether disconnector or breaker truck is
either open (in test position) or close (in service position). This output, together with
the open earth-switch and non-active trip signals, activates the close-enable signal to
the circuit breaker control function block. The open operation for circuit breaker is
always enabled.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
REF615 standard configurations
DCSXSWI1
POSOPEN
OPENPOS
POSCLOSE
CLOSEPOS
OKPOS
AND6
B1
O
B2
B3
B4
B5
B6
ESSXSWI1
POSOPEN
OPENPOS
POSCLOSE
CLOSEPOS
OKPOS
OR6
B1
O
B2
B3
B4
B5
B6
Section 3
DCSXSWI1_OKPOS
DC1_CLOSE_ENABLE
ESSXSWI1_OPENPOS
ES1_CLOSE_ENABLED
345