ABB relion REF615 Applications Manual page 234

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
228
Table 46:
Default connections for binary inputs
Binary input
Description
X110-BI1
Busbar VT secondary MCB open
X110-BI2
Line VT secondary MCB open
X110-BI3
Circuit breaker low gas pressure indication
X110-BI4
Circuit breaker spring charged indication
X110-BI5
Circuit breaker truck in (service position) indication
X110-BI6
Circuit breaker truck out (test position) indication
X110-BI7
Earthing switch closed indication
X110-BI8
Earthing switch open indication
X120-BI1
Blocking of overcurrent instantaneous stage
X120-BI2
Circuit breaker closed indication
X120-BI3
Circuit breaker open indication
X120-BI4
Lock-out reset
Table 47:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Breaker failure backup trip to upstream breaker
X100-SO1
General start indication
X100-SO2
General operate indication
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2
X110-SO1
Upstream overcurrent blocking
X110-SO2
Overcurrent operate alarm
X110-SO3
Earth-fault operate alarm
X110-SO4
Voltage protection operate alarm
X110-HSO1
Arc protection instance 1 operate activated
X110-HSO2
Arc protection instance 2 operate activated
X110-HSO3
Arc protection instance 3 operate activated
Table 48:
Default connections for LEDs
LED
Description
1
Overcurrent protection operated
2
Earth-fault protection operated
3
Combined protection operated indication
4
Synchronism or energizing check OK
5
Frequency protection
6
Circuit breaker failure protection backup protection operated
Table continues on next page
1MRS756378 S
REF615
Application Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents