ABB relion REF615 Applications Manual page 368

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
PHIPTOC1_OPERATE
PHHPTOC1_OPERATE
PHLPTOC2_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
X120_BI2_CB_CLOSED
GUID-39F151C5-77E0-4268-99D6-0F172571155C V1 EN
Figure 570:
Circuit breaker failure protection function
362
GUID-5995DF50-E527-4A1A-8704-5D0E283131CF V1 EN
Figure 569:
Thermal overcurrent protection function
Circuit breaker failure protection CCBRBRF1 is initiated via the START input by
number of different protection functions available in the IED. The breaker failure
protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents.
The circuit breaker failure protection function has two operating outputs: TRRET and
TRBU. The TRRET operate output is used for retripping its own breaker through
TRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breaker
feeding upstream. For this purpose, the TRBU operate output signal is connected to the
binary output X100:PO2.
OR6
B1
O
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
Three arc protection ARCSARC1...3 stages are included as an optional function. The
arc protection offers individual function blocks for three arc sensors that can be
connected to the IED. Each arc protection function block has two different operation
modes, that is, with or without the phase and residual current check.
The operate signals from ARCSARC1...3 are connected to both trip logic TRPPTRC1
and TRPPTRC2. If the IED has been ordered with high speed binary outputs, the
individual operate signals from ARCSARC1...3 are connected to dedicated trip logic
TRPPTRC3...5. The outputs of TRPPTRC3...5 are available at high speed outputs
X110:HSO1, X110:HSO2 and X110:HSO3.
T1PTTR1
BLK_OPR
OPERATE
ENA_MULT
START
TEMP_AMB
ALARM
BLK_CLOSE
OR6
B1
O
B2
B3
B4
B5
B6
T1PTTR1_OPERATE
T1PTTR1_START
T1PTTR1_ALARM
CCBRBRF1
BLOCK
CB_FAULT_AL
START
TRBU
POSCLOSE
TRRET
CB_FAULT
Application Manual
1MRS756378 S
CCBRBRF1_TRBU
CCBRBRF1_TRRET
REF615

Hide quick links:

Advertisement

Table of Contents
loading