ABB relion REF615 Applications Manual page 370

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
PDNSPTOC1_OPERATE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
CBXCBR1_SELECTED
X110_BI3_GAS_PRESSURE_ALARM
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
GUID-54D649CF-D62C-45B9-8371-06270522AB89 V1 EN
Figure 572:
Autoreclosing function
364
control command to the circuit breaker, either local or remote, also blocks the
autoreclosing function via the CBXCBR1-SELECTED signal.
The circuit breaker availability for the autoreclosing sequence is expressed with the
CB_READY input in DARREC1. The signal, and other required signals, are connected
to the CB spring charged binary inputs in this configuration. The open command from
the autorecloser is connected directly to binary output X100:PO3, whereas the close
command is connected directly to the binary output X100:PO1.
X110_BI2_EXT_START_AUTORECLOSE
X120_BI3_CB_OPENED
X110_BI4_CB_SPRING_CHARGED
OR6
B1
O
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
General start and operate from all the functions are connected to minimum pulse timer
TPGAPC1 for setting the minimum pulse length for the outputs. The output from
TPGAPC1 is connected to binary outputs
INIT_1
PHIPTOC1_OPERATE
INIT_2
PHLPTOC2_OPERATE
INIT_3
PHHPTOC1_OPERATE
INIT_4
EFLPTOC1_OPERATE
INIT_5
EFHPTOC1_OPERATE
INIT_6
DEL_INIT_2
DEL_INIT_3
DEL_INIT_4
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
INHIBIT_RECL
RECL_ON
SYNC
OR
B1
O
B2
1MRS756378 S
DARREC1
OPEN_CB
DARREC1_OPEN_CB
CLOSE_CB
DARREC1_CLOSE_CB
CMD_WAIT
INPRO
DARREC1_INPRO
LOCKED
PROT_CRD
UNSUC_RECL
DARREC1_UNSUC_RECL
AR_ON
READY
ACTIVE
Application Manual
REF615