ABB relion REF615 Applications Manual page 136

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
130
X110_BI8_ES1_OPENED
X110_BI7_ES1_CLOSED
GUID-5602152F-6F87-4D49-86AF-E4968E4B88BB V1 EN
Figure 150:
Earthing switch 1
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earth-switch position status, status of the trip logics,
gas pressure alarm and circuit breaker spring charging status.
The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is
definitely either open (in test position) or close (in service position). This output,
together with the open earth-switch and non-active trip signals, activates the close-
enable signal to the circuit breaker control function block. The open operation for
circuit breaker is always enabled.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position.
SYNC_ITL_BYP overrides, for example, active interlocking conditions when the
circuit breaker truck is closed in service position.
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
TRUE
CBXCBR1_ENA_CLOSE
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
GUID-DBBDB84F-27F4-4034-A21B-01CD29A82207 V2 EN
Figure 151:
Circuit breaker 1
Connect the additional signals required by the application for closing
and opening of the circuit breaker.
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-63F53739-3A34-4391-9F0C-0833324FAEA3 V1 EN
Figure 152:
Signals for closing coil of circuit breaker 1
ESSXSWI1
POSOPEN
OPENPOS
POSCLOSE
CLOSEPOS
OKPOS
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
OR
B1
O
B2
1MRS756378 S
ESSXSWI1_OPENPOS
CBXCBR1_SELECTED
CBXCBR1_EXE_OP
CBXCBR1_EXE_CL
CB_CLOSE_COMMAND
REF615