1MRS756378 S
REF615
Application Manual
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
TRUE
CBXCBR1_ENA_CLOSE
FALSE
CBXCBR1_BLK_CLOSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
GUID-9A8F2948-56E2-432A-BFDC-9DAD36F414DC V2 EN
Figure 255:
Circuit breaker 1 control logic
CBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-4A45B0DB-3CB8-4190-BA99-EE2BF15C696D V1 EN
Figure 256:
Signal for closing coil of circuit breaker 1
CBXCBR1_EXE_OP
TRPPTRC1_TRIP
DARREC1_OPEN_CB
GUID-5A234526-696C-4CC5-B39C-387D1AF6D3EB V1 EN
Figure 257:
Signal for opening coil of circuit breaker 1
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI3_GAS_PRESSURE_ALARM
GUID-ADC3C9F4-02A8-4B00-8577-66728AE4ADDA V1 EN
Figure 258:
Circuit breaker 1 close enable logic
Connect the higher-priority conditions before enabling the closing of
circuit breaker. These conditions cannot be bypassed using bypass
feature of the function.
REF615 standard configurations
CBXCBR1
POSOPEN
SELECTED
POSCLOSE
EXE_OP
ENA_OPEN
EXE_CL
ENA_CLOSE
OP_REQ
BLK_OPEN
CL_REQ
BLK_CLOSE
OPENPOS
AU_OPEN
CLOSEPOS
AU_CLOSE
OKPOS
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
OR
B1
B2
OR6
B1
B2
B3
B4
B5
B6
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
X110_BI4_CB_SPRING_CHARGED
NOT
IN
OUT
NOT
IN
OUT
NOT
IN
OUT
Section 3
CBXCBR1_SELECTED
CBXCBR1_EXE_OP
CBXCBR1_EXE_CL
O
CB_CLOSE_COMMAND
O
CB_OPEN_COMMAND
AND6
B1
O
CBXCBR1_ENA_CLOSE
B2
B3
B4
B5
B6
189