Functional Diagrams - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.6.3
118
Channel
ID text
16
PHIPTOC1 - operate
PHHPTOC1 - operate
PHHPTOC2 - operate
PHLPTOC1 - operate
17
NSPTOC1 - operate
NSPTOC2 - operate
18
EFLPTOC1 - operate
EFHPTOC1 - operate
EFIPTOC1 - operate
19
X110BI2 - ext start AutoReclose
20
EFLPTOC2 - operate
21
PDNSPTOC1 - operate
22
INRPHAR1 - blk2h
23
T1PTTR1 - operate
24
ARCSARC1 - ARC flt det
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
25
ARCSARC1 - operate
26
ARCSARC2 - operate
27
ARCSARC3 - operate
28
DARREC1 - inpro
29
DARREC1 - close CB
30
DARREC1 - unsuc recl
31
X120BI1 - ext OC blocking
32
X120BI2 - CB closed
33
X120BI3 - CB opened

Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED's standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder's parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
1MRS756378 S
Level trigger mode
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Positive or Rising
Positive or Rising
Positive or Rising
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
Level trigger off
REF615
Application Manual