Section 3
REF615 standard configurations
3.4.3.2
86
assigned to RST_LKOUT input of both the trip logic to enable external reset with a
push button. Three other trip logics TRPPTRC3...4 are also available if the IED is
ordered with high speed binary outputs options.
OR6
B1
PHIPTOC1_OPERATE
B2
PHLPTOC1_OPERATE
B3
PHHPTOC1_OPERATE
B4
PHHPTOC2_OPERATE
B5
NSPTOC1_OPERATE
B6
NSPTOC2_OPERATE
OR6
B1
DEFHPDEF1_OPERATE
B2
DEFLPDEF1_OPERATE
B3
DEFLPDEF2_OPERATE
B4
EFPADM1_OPERATE
B5
EFPADM2_OPERATE
B6
EFPADM3_OPERATE
OR6
B1
INTRPTEF1_OPERATE
B2
EFHPTOC1_OPERATE
B3
PDNSPTOC1_OPERATE
B4
ROVPTOV1_OPERATE
B5
ROVPTOV2_OPERATE
B6
ROVPTOV3_OPERATE
OR6
B1
WPWDE1_OPERATE
B2
WPWDE2_OPERATE
B3
WPWDE3_OPERATE
B4
ARCSARC1_OPERATE
B5
ARCSARC2_OPERATE
B6
ARCSARC3_OPERATE
GUID-AF22589C-B208-45F8-ADB9-D925C183367A V1 EN
Figure 69:
Trip logic TRPPTRC1
OR6
B1
PHIPTOC1_OPERATE
B2
PHLPTOC1_OPERATE
B3
PHHPTOC1_OPERATE
B4
PHHPTOC2_OPERATE
B5
NSPTOC1_OPERATE
B6
NSPTOC2_OPERATE
OR6
B1
DEFHPDEF1_OPERATE
B2
DEFLPDEF1_OPERATE
B3
DEFLPDEF2_OPERATE
B4
EFPADM1_OPERATE
B5
EFPADM2_OPERATE
B6
EFPADM3_OPERATE
OR6
B1
INTRPTEF1_OPERATE
B2
EFHPTOC1_OPERATE
B3
PDNSPTOC1_OPERATE
B4
ROVPTOV1_OPERATE
B5
ROVPTOV2_OPERATE
B6
ROVPTOV3_OPERATE
OR6
B1
B2
CCBRBRF1_TRRET
B3
WPWDE1_OPERATE
B4
WPWDE2_OPERATE
B5
WPWDE3_OPERATE
B6
OR6
B1
ARCSARC1_OPERATE
B2
ARCSARC2_OPERATE
B3
ARCSARC3_OPERATE
B4
B5
B6
GUID-1D960595-DAB7-44B3-8D6A-36CB54AAFCB6 V1 EN
Figure 70:
Trip logic TRPPTRC2
Functional diagrams for disturbance recorder
The START and OPERATE outputs from the protection stages are routed to trigger the
disturbance recorder or, alternatively, only to be recorded by the disturbance recorder
OR6
O
B1
B2
B3
B4
B5
B6
O
O
O
OR6
O
B1
O
B2
B3
B4
B5
B6
O
O
O
O
1MRS756378 S
TRPPTRC1
BLOCK
TRIP
O
OPERATE
CL_LKOUT
RST_LKOUT
TRPPTRC2
BLOCK
TRIP
OPERATE
CL_LKOUT
RST_LKOUT
Application Manual
TRPPTRC1_TRIP
TRPPTRC2_TRIP
REF615