Section 3
REF615 standard configurations
292
Table 56:
Default connections for binary inputs
Binary input
Description
X110-BI1
Busbar VT secondary MCB open
X110-BI2
Line VT secondary MCB open
X110-BI3
Circuit breaker low gas pressure indication
X110-BI4
Circuit breaker spring charged indication
X110-BI5
Circuit breaker truck in (service position) indication
X110-BI6
Circuit breaker truck out (test position) indication
X110-BI7
Earthing switch closed indication
X110-BI8
Earthing switch open indication
X130-BI1
Blocking of overcurrent instantaneous stage
X130-BI2
Circuit breaker closed position indication
X130-BI3
Circuit breaker open position indication
X130-BI4
Lock-out reset
Table 57:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Breaker failure backup trip to upstream breaker
X100-SO1
General start indication
X100-SO2
General operate indication
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2 or EFLPTOC2 operated
X110-SO1
-
X110-SO2
Overcurrent operate alarm
X110-SO3
Earth-fault operate alarm
X110-SO4
Voltage or frequency protection operate alarm
X110-HSO1
Arc protection instance 1 operate activated
X110-HSO2
Arc protection instance 2 operate activated
X110-HSO3
Arc protection instance 3 operate activated
Table 58:
Default connections for LEDs
LED
Description
1
Overcurrent protection operate
2
Earth-fault protection operate
3
Combined protection operation indication
4
Synchronism or energizing check Ok
5
Frequency protection operated
6
Circuit breaker failure protection operated
Table continues on next page
1MRS756378 S
REF615
Application Manual