ABB relion REF615 Applications Manual page 129

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
REF615
Application Manual
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
GUID-C29D3E5A-5875-413D-B8D1-09C2FDDEF2D3 V1 EN
Figure 137:
Arc protection function
ARCSARC1_OPERATE
X120_BI4_RST_LOCKOUT
ARCSARC2_OPERATE
X120_BI4_RST_LOCKOUT
ARCSARC3_OPERATE
X120_BI4_RST_LOCKOUT
GUID-075DA511-6800-4425-85CE-2B1BD69661FC V1 EN
Figure 138:
Arc protection with dedicated HSO
The optional autoreclosing function is configured to be initiated by operate signals
from a number of protection stages through the INIT_1...5 inputs. The INIT_6
input in the autoreclosing function block is controlled by a binary input X110: BI2
enabling the use of the external autoreclosing start command. It is possible to create
individual autoreclose sequences for each input.
REF615 standard configurations
ARCSARC1
BLOCK
OPERATE
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
ARCSARC2
BLOCK
OPERATE
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
ARCSARC3
BLOCK
OPERATE
REM_FLT_ARC
ARC_FLT_DET
OPR_MODE
OR6
B1
O
B2
B3
B4
B5
B6
TRPPTRC3
BLOCK
TRIP
OPERATE
CL_LKOUT
RST_LKOUT
TRPPTRC4
BLOCK
TRIP
OPERATE
CL_LKOUT
RST_LKOUT
TRPPTRC5
BLOCK
TRIP
OPERATE
CL_LKOUT
RST_LKOUT
Section 3
ARCSARC1_OPERATE
ARCSARC1_ARC_FLT_DET
ARCSARC2_OPERATE
ARCSARC2_ARC_FLT_DET
ARCSARC3_OPERATE
ARCSARC3_ARC_FLT_DET
ARCSARC_OPERATE
TRPPTRC3_TRIP
TRPPTRC4_TRIP
TRPPTRC5_TRIP
123