Functional Diagrams For Measurement Functions - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
3.14.3.5
REF615
Application Manual
DCSXSWI1_OKPOS
ESSXSWI1_OPENPOS
X110_BI4_CB_SPRING_CHARGED
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI3_GAS_PRESSURE_ALARM
GUID-4BD1BA07-C7A7-4510-BAB9-DBF3BABD1A02 V1 EN
Figure 587:
Circuit breaker close enable logic
The configuration includes the logic for generating circuit breaker external closing
and opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command and
modify it according to the application.
Connect the additional signal for closing and opening of circuit
breaker in local or remote mode if applicable for the configuration.
B1
CONTROL_LOCAL
B2
FALSE
B1
CONTROL_REMOTE
B2
FALSE
GUID-065B8F38-D535-4FBF-B2B5-9FB82191614C V1 EN
Figure 588:
External closing command for circuit breaker 1
CONTROL_LOCAL
FALSE
CONTROL_REMOTE
FALSE
GUID-0978DD77-5996-4E3C-BFCE-E0726ED2BC9A V1 EN
Figure 589:
External opening command for circuit breaker 1

Functional diagrams for measurement functions

The phase current inputs to the IED are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card in
the back panel. The sequence current measurement CSMSQI1 measures the sequence
current and the residual current measurement RESCMMXU1 measures the residual
current.
REF615 standard configurations
NOT
IN
OUT
NOT
IN
OUT
NOT
IN
OUT
AND
O
B1
B2
AND
O
AND
B1
O
B2
B1
B2
AND
B1
O
B2
Section 3
AND6
B1
O
CBXCBR1_ENA_CLOSE
B2
B3
B4
B5
B6
OR
O
CBXCBR1_AU_CLOSE
OR
O
CBXBCR1_AU_OPEN
371