Functional Diagrams For Control And Interlocking - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.13.3.4
344
It is assumed that there is an external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR1_ALARM
TCSSCBR2_ALARM
GUID-5248E2A0-0212-41A0-9124-40151EA71FA9 V1 EN
Figure 535:
Trip circuit supervision function
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI3_CB_OPENED
GUID-1C0AD672-5573-4348-AADA-DB5EA1326A76 V1 EN
Figure 536:
Logic for blocking trip circuit supervision

Functional diagrams for control and interlocking

Two types of disconnector and earthing switch function blocks are available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration. The disconnector (CB truck) and line side earthing switch
status information are connected to DCSXSWI1 and ESSXSI1.
The configuration includes closed enable interlocking logic for disconnector and
earthing switch. These signals are available for binary outputs X100:SO1 and
X100:SO2.
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
OR
B1
O
B2
OR6
B1
O
B2
B3
B4
B5
B6
1MRS756378 S
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR_ALARM
TCSSCBR_BLOCKING