Autoreclosing function
60
The optional autoreclosing function is configured to be initiated by operate signals
from a number of protection stages through the INIT_1...5 inputs. It is possible to
create individual autoreclose sequences for each input.
The autoreclosing function can be inhibited with the INHIBIT_RECL input. By
default, few selected protection function operations are connected to this input. A
control command to the circuit breaker, either local or remote, also blocks the
autoreclosing function via the CBXCBR1_SELECTED signal.
The circuit breaker availability for the autoreclosing sequence is expressed with the
CB_READY input in DARREC1. This signal is not connected in the configuration.
The open command from the autorecloser is connected directly to binary output
X100:PO3, whereas the close command is connected directly to binary output
X100:PO1.
Set the parameters for DARREC1 properly.
Check the initialization signals of DARREC1.
OR6
B1
O
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
PHIPTOC1_OPERATE
PHHPTOC2_OPERATE
PHHPTOC1_OPERATE
X120_BI3_CB_OPENED
OR
B1
O
B2
DARREC1
INIT_1
OPEN_CB
INIT_2
CLOSE_CB
INIT_3
CMD_WAIT
INIT_4
INPRO
INIT_5
LOCKED
INIT_6
PROT_CRD
DEL_INIT_2
UNSUC_RECL
DEL_INIT_3
AR_ON
DEL_INIT_4
READY
BLK_RECL_T
ACTIVE
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
INHIBIT_RECL
RECL_ON
SYNC
1MRS756378 S
DARREC1_OPEN_CB
DARREC1_CLOSE_CB
DARREC1_INPRO
DARREC1_UNSUC_RECL
REF615