Figure 445:
Timer logic for voltage and frequency operate pulse

Other functions

The configuration includes few instances of multipurpose protection MAPGAPC,
runtime counter for machines and devices MDSOPT and different types of timers and
control functions. These functions are not included in application configuration but
they can be added based on the system requirements.
Standard configuration K
Applications
The standard configuration for directional overcurrent and directional earth-fault
protection with phase voltage-based measurements, high-impendance restricted
earth-fault protection, undervoltage and overvoltage protection, frequency protection
and measurement functions is mainly intended for cable and overhead-line feeder
applications in isolated or resonant-earthed distribution networks. The configuration
also includes additional options for selecting earth-fault protection based on
admittance, wattmetric or harmonic-based principles.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality using PCM600.