Section 3
REF615 standard configurations
324
Table 61:
Default connections for binary inputs
Binary input
Description
X110-BI1
Circuit breaker plug not inserted
X110-BI2
Circuit breaker spring discharged
X110-BI3
Circuit breaker open indication
X110-BI4
Circuit breaker closed indication
X110-BI5
Circuit breaker truck out (test position) indication
X110-BI6
Circuit breaker truck in (service position) indication
X110-BI7
Earthing switch open indication
X110-BI8
Earthing switch closed indication
Table 62:
Default connections for binary outputs
Binary output
Description
X100-PO1
Release for circuit breaker closing
X100-PO2
Circuit breaker close command
X100-SO1
Release for circuit breaker tuck
X100-SO2
Release for earthing switch
X100-PO3
Circuit breaker open command
X100-PO4
Breaker failure backup trip to upstream breaker
X110-HSO1
Arc protection instance 1 operate activated
X110-HSO2
Arc protection instance 2 operate activated
X110-HSO3
Arc protection instance 3 operate activated
Table 63:
Default connections for LEDs
LED
Description
1
Circuit breaker close enabled
2
Short circuit protection operated
3
Earth-fault protection operated
4
Current unbalance protection operated
5
NPS or PPS voltage protection operated
6
Overvoltage or residual overvoltage protection operated
7
Thermal overload alarm
8
Undervoltage or frequency protection operated
9
Supervision alarm
10
Circuit breaker condition monitoring alarm
11
-
1MRS756378 S
REF615
Application Manual