Functional Diagrams For Protection - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.10.3.1
232

Functional diagrams for protection

The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four non-directional overcurrent stages are offered for overcurrent and short-circuit
protection. Three-phase non-directional overcurrent protection, instantaneous stage,
PHIPTOC1 can be blocked by energizing the binary input X120:BI1.
X120_BI1_EXT_OC_BLOCKING
PHIPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHLPTOC1_OPERATE
GUID-4418FE50-A21E-4DA3-B13C-97D408EB4CFA V1 EN
Figure 334:
Overcurrent protection function
The upstream blocking from the start of the second high stage of three-phase non-
directional overcurrent protection PHHPTOC2 is connected to the binary output
X110:SO1. This output can be used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.
PHHPTOC2_START
GUID-9B85F4BF-82D4-4867-B89B-1E73F145341C V1 EN
Figure 335:
Upstream blocking logic
PHIPTOC1
BLOCK
OPERATE
ENA_MULT
START
PHHPTOC1
BLOCK
OPERATE
ENA_MULT
START
PHHPTOC2
BLOCK
OPERATE
ENA_MULT
START
PHLPTOC1
BLOCK
OPERATE
ENA_MULT
START
OR6
B1
B2
B3
B4
B5
B6
OR6
B1
O
B2
B3
B4
B5
B6
1MRS756378 S
PHIPTOC1_OPERATE
PHIPTOC1_START
PHHPTOC1_OPERATE
PHHPTOC1_START
PHHPTOC2_OPERATE
PHHPTOC2_START
PHLPTOC1_OPERATE
PHLPTOC1_START
O
PHxPTOC_OPERATE
UPSTEAM_OC_BLOCKING
REF615
Application Manual