Table 41:
Default connections for binary inputs
Binary input
Description
X110-BI1
Circuit breaker closed indication
X110-BI2
Circuit breaker open indication
X110-BI3
Circuit breaker low gas pressure indication
X110-BI4
Circuit breaker spring charged indication
X110-BI5
Circuit breaker truck in (service position) indication
X110-BI6
Circuit breaker truck out (test position) indication
X110-BI7
Earthing switch closed indication
X110-BI8
Earthing switch open indication
Table 42:
Default connections for binary outputs
Binary output
Description
X100-PO1
Close circuit breaker
X100-PO2
Breaker failure backup trip to upstream breaker
X100-SO1
General start indication
X100-SO2
General operate indication
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open circuit breaker/trip coil 2
X110-SO1
Upstream overcurrent blocking
X110-SO2
Overcurrent operate alarm
X110-SO3
Earth-fault operate alarm
X110-SO4
Voltage protection operate alarm
X110-HSO1
Arc protection instance 1 operate activated
X110-HSO2
Arc protection instance 2 operate activated
X110-HSO3
Arc protection instance 3 operate activated
Table 43:
Default connections for LEDs
LED
Description
1
Overcurrent protection operated
2
Earth-fault protection operated
3
Voltage protection operated
4
Negative sequence overcurrent or phase discontinuity protection operated
5
Thermal overload alarm
6
Circuit breaker failure protection backup protection operated
7
Disturbance recorder triggered
8
Circuit breaker condition monitoring alarm
9
Supervision alarm
10
Arc fault detected
11
Autoreclose in progress
REF615 standard configurations
Section 3
199