Functional Diagrams For Control And Interlocking - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
3.10.3.4
REF615
Application Manual
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
GUID-75C22AA4-4F3D-4F1E-9E7F-82C1AB76D23F V1 EN
Figure 357:
Logic for blocking of trip circuit supervision

Functional diagrams for control and interlocking

The main purpose of the synchronism and energizing check SECRSYN is to provide
control over the closing of the circuit breakers in power networks to prevent the
closing, if the conditions for synchronism are not detected. The energizing function
allows closing, for example, when one side of the breaker is dead.
SECRSYN measures the bus and line voltages and compares them to the set
conditions. When all the measured quantities are within set limits, the output
SYNC_OK is activated for allowing closing or closing the circuit breaker. The
SYNC_OK output signal of SECRSYN is connected to ENA_CLOSE input of
CBXCBR through control logic. The function is block in case of line side or bus side
MCB is open.
BLOCK_SECRSYN1
X110_BI2_LINE_VT_MCB_OPEN
X110_BI1_BUS_VT_MCB_OPEN
GUID-1054A5E9-E611-4D4B-82B5-5FD0AFE8CF66 V1 EN
Figure 358:
Synchrocheck function
Two types of disconnector and earthing switch function blocks are available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration. The disconnector (CB truck) and line side earthing switch
status information is connected to DCSXSWI1 and ESSXSI1.
X110_BI6_CB_TRUCK_IN_TEST
X110_BI5_CB_TRUCK_IN_SERVICE
GUID-A84A3976-BDA8-4343-96F1-1E436AF74BBE V1 EN
Figure 359:
Disconnector control logic
REF615 standard configurations
OR6
B1
O
B2
B3
B4
B5
B6
SECRSYN1
BLOCK
SYNC_INPRO
CL_COMMAND
SYNC_OK
BYPASS
CL_FAIL_AL
CMD_FAIL_AL
LLDB
LLLB
DLLB
DLDB
OR
B1
O
B2
DCSXSWI1
POSOPEN
OPENPOS
POSCLOSE
CLOSEPOS
OKPOS
Section 3
TCSSCBR_BLOCKING
SECRSYN1_SYNC_INPRO
SECRSYN1_SYNC_OK
SECRSYN1_CL_FAIL_AL
SECRSYN1_CMD_FAIL_AL
BLOCK_SECRSYN1
DCSXSWI1_OKPOS
247