ABB relion REF615 Applications Manual page 27

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

1MRS756378 S
REF615
Application Manual
Table 2:
Plug-in unit and case
Main unit
Slot ID
Content options
Plug-in
-
HMI
unit
X100
Auxiliary power/BO
module
X110
BIO module
X120
AI/BI module
Table continues on next page
REF615 overview
Small (5 lines, 20 characters)
Large (10 lines, 20 characters) with SLD
Small Chinese (3 lines, 8 or more characters)
Large Chinese (7 lines, 8 or more characters) with SLD
48-250 V DC/100-240 V AC; or 24-60 V DC
2 normally-open PO contacts
1 change-over SO contacts
1 normally-open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
Only with configurations B, D, E, F, G, H, J, K, L and N:
8 binary inputs
4 SO contacts
Only with configurations B, D, E, F, G, H, J, K, L and N:
8 binary inputs
3 HSO contacts
Only with configurations A and B:
3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)
1 residual voltage input (60-210 V)
3 binary inputs
Only with configurations C, D, E, F, H, J and N:
3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)
4 binary inputs
Only with configuration K:
6 phase current inputs (1/5 A)
1 residual current input (1/5 A)
Section 2
1)
1)
21