Functional Diagrams For Protection - ABB relion REF615 Applications Manual

Feeder protection and control relion 615 series
Hide thumbs Also See for relion REF615:
Table of Contents

Advertisement

Section 3
REF615 standard configurations
3.11.3.1
262
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.

Functional diagrams for protection

The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection. Three
of these include directional functionality DPHxPDOC. Three-phase non-directional
overcurrent protection, instantaneous stage, PHIPTOC1 can be blocked by energizing
the binary input X120:BI1.
X120_BI1_EXT_OC_BLOCKING
GUID-B16AE694-A1BF-450D-AFA8-BE6CDEC14F31 V1 EN
Figure 386:
Overcurrent protection function
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC2_OPERATE
GUID-D8B8656A-F5D7-4449-94B4-CFE402EDE482 V1 EN
Figure 387:
Directional overcurrent protection function
PHIPTOC1
BLOCK
OPERATE
ENA_MULT
START
DPHHPDOC1
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC1
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC2
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
OR6
B1
O
B2
B3
B4
B5
B6
1MRS756378 S
PHIPTOC1_OPERATE
PHIPTOC1_START
DPHHPDOC1_OPERATE
DPHHPDOC1_START
DPHLPDOC1_OPERATE
DPHLPDOC1_START
DPHLPDOC2_OPERATE
DPHLPDOC2_START
DPHxPDOC_OPERATE
REF615
Application Manual