Section 3
REF615 standard configurations
3.12.3.1
296

Functional diagrams for protection

The functional diagrams describe the protection functionality of the IEDs in detail and
according to the factory set default connections.
Five overcurrent stages are offered for overcurrent and short-circuit protection. Two
of them include directional functionality DPHxPDOC. Three-phase non-directional
overcurrent protection, instantaneous stage, PHIPTOC1 can be blocked by energizing
the binary input X130: BI1.
X130_BI1_EXT_OC_BLOCKING
PHIPTOC1_OPERATE
PHHPTOC1_OPERATE
PHLPTOC1_OPERATE
GUID-BD0A9F06-B0A0-4DA9-B6C7-FDED4A790786 V1 EN
Figure 447:
Overcurrent protection function
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
GUID-4F6D1599-A6AE-4742-8599-84B85535E2B5 V1 EN
Figure 448:
Directional overcurrent protection function
PHIPTOC1
BLOCK
OPERATE
ENA_MULT
START
PHHPTOC1
BLOCK
OPERATE
ENA_MULT
START
PHLPTOC1
BLOCK
OPERATE
ENA_MULT
START
OR6
B1
O
B2
B3
B4
B5
B6
DPHHPDOC1
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC1
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
OR
B1
O
B2
1MRS756378 S
PHIPTOC1_OPERATE
PHIPTOC1_START
PHHPTOC1_OPERATE
PHHPTOC1_START
PHLPTOC1_OPERATE
PHLPTOC1_START
PHxPTOC_OPERATE
DPHHPDOC1_OPERATE
DPHHPDOC1_START
DPHLPDOC1_OPERATE
DPHLPDOC1_START
DPHxPDOC_OPERATE
REF615