REC650
Commissioning Manual
Testing functionality

Testing disturbance report

Introduction

The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
Fault locator
Trip value recorder
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is
not possible to only switch these sub-functions off. The disturbance report function
is switched off (parameter Operation = Off) in PCM600 or the local HMI under
Main menu/Settings/IED Settings/Monitoring/Disturbance Report/
1:DRPRDRE.

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or
inactive. If the disturbance recorder is turned on during test mode, recordings will
be made. When test mode is switched off all recordings made during the test
session are cleared.
Setting OpModeTest for the control of the disturbance recorder during test mode
are located in the local HMI under:
Main menu/Settings/IED Settings/Monitoring/Disturbance Report/
1:DRPRDRE

Disturbance recorder (DR)

A Manual Trig can be started at any time. This results in a recording of the actual
values from all recorded channels.
The Manual Trig can be initiated in two ways:
1.
From the local HMI under: Main menu/Disturbance records.
Section 5
Testing functionality
35