6. Trouble shooting

6.1

PS D without electronic overload protection

6.1.1

Different status on LED's and signal relays

LED on
LED off
See
LED's
next
page
F1
I
On
T
II
F1
On
T
F1
III
On
T
IV
F1
On
T
V
F1
On
T
VI
F1
On
T
F1
VII
On
T
VIII
F1
On
T
IX
F1
On
T
Signal relay energised
Signal relay not activated
Signal relays
Run
TOR
Fault
F2
R
P
F2
R
P
F2
R
P
F2
R
P
F2
R
P
F2
R
P
F2
R
P
F2
R
P
F2
R
P
No control voltage on terminal 1 and 2
Control voltage supplied
Ready for start
a)
Control voltage supplied and start signal is given.
b)
Control voltage supplied and making ramp down
during stop
Normal continuous run.
100% voltage to the motor
By-pass signal relay energised
Normal continuous run.
100% voltage to the motor
By-pass signal relay energised
Power factor optimising (energy saving) activated
(Switch PF in position-Y,(On)
Control voltage supplied and start signal is given.
Fault F1
( See also fault code tables and flow diagram)
a)
Phase loss
b)
Switched off by the function
"High current switch off" The switch SC has to be in Y-
position (On)
Reset
Via stop signal
Control voltage supplied.
Fault F2
( See also fault code tables and flow diagram)
a)
Over temperature on heat sink
b)
Internal fault PCB
Reset
Via stop signal
Control voltage supplied.
Fault F1+F2 ( See also fault code tables and flow diagram)
a)
Shorted thyristor
b)
Semiconductor not conducting
Continuous run with shorted thyristor
(Switch PF must be in N-position, Off)