Group 15: Analog Output

Analog output is used to output the value of any parameter of the Operating Data group (Group 1) as
a current signal. Output current minimum and maximum values are configurable, as are the allowed
minimum and maximum values for the observed parameter.
If analog output content maximum value (parameter 1503) is set to less than minimum value
(parameter 1502), output current is inversely proportional to the value of the observed parameter.
Code Description
1501 AO CONTENT
Content for analog output. Number of any parameter of the Operating Data group (Group 01).
1502 AO CONTENT MIN
Analog output content minimum. Display depends on parameter 1501.
1503 AO CONTENT MAX
Analog output content maximum. Display depends on parameter 1501.
1504 MINIMUM AO
Minimum output current.
1505 MAXIMUM AO
Maximum output current.
1506 AO FILTER
Filter time constant for AO.
Figure 25 Analog output scaling.
70
AO (mA)
1505
1504
1502
AO (mA)
1505
1504
1503
AO content
1503
AO content
1502
ACS 400 User's Manual