Alpha 6000S series User Manual page 52

Table of Contents

Advertisement

P1: Start-stop control
Function
Parameter
code
P1.00
Starting mode
Starting
P1.01
frequency
Starting
P1.02
frequency hold
time
Start DC
P1.03
braking current
Start DC
P1.04
braking time
Start preset
P1.05
frequency
Preset
P1.06
frequency hold
time
Acceleration
and
P1.07
deceleration
mode
S curve start
P1.08
time
51
LCD display
0: Start from the start
frequency
1: First brake (excitation),
and then start at the start
frequency
2: Rotating speed
connected to PG or
rotating speed tracking
Starting mode
board, 3004GB and below
models do not support
rotating speed tracking
board)
Note: The startup procedure
includes initial power-on,
power restoration after
instantaneous stop, external
fault reset, and all startup
procedure after free stopping
Starting
0.10~60.00Hz
frequency
Start hold time
0.0~10.0s
Depend on model
0-100.0% of rated current of
the motor.
It is active only in V/F
control mode, the upper limit
is 80% of the nominal current
of inverter or smaller one
Start braking
among the nominal current of
current
the motor; in vector control
mode, the current is
determined by P8.00
pre-excitation current
compensation factor; when
the set value is less than
100%, perform it at 100%
Start braking
0.0~30.0s
time
Start preset
0.00-maximum frequency
frequency
Preset
frequency hold
0.0~3600.0s
time
Acceleration
and
0: Linear 1: S curve
deceleration
2: (Reserve) 3: (Reserve)
mode
10.0-50.0 % (acceleration and
S curve start
deceleration time )
segment
P1.08+P1.09≤90%
Setting range
tracking (must be
Chapter 4 Parameter Index
Factory setting
Mod.
0
0.50Hz
0.0s
0.0%
0.1s
0.00Hz
×
0.0s
×
0
20.0%
MODBUS
address
0200
0201
0202
0203
0204
0205
0206
0207
0208