Chapter 5 Detailed Function Introductions
Phys ical value
corres ponding to Max
analog value Input%
Phys ical value
corres ponding to Min
analog value Input%
Note 2:
When P4.00 is set to 1, 2, or 3, the function of P4.01~P4.04, P4.06~P4.09 and P4.11~P4.14 are combined for
one physical value, which is different to Note 1. User can define their own nonlinear curves by setting these
parameters. Six points can be set on the curve. As shown in Figure. 5-4-2. In addition, the setting value to
P4.01, P4.03, P4.06, P4.08, P4.11, P4.13 must increase in order.
P hysical value corresponding t o
Note 3:
The input filter time constant is used for digital filter of the input signal, in order to avoid interference of the
system.
The bigger the filter time constant, the higher the immunity level and the longer the response time is. On the
contrary, the smaller the time constant, the shorter the response time and the lower the immunity level is. If
the best setting is not clear, you can adjust setting value according to the status of control stability and
response delay time.
P4.21 AO1 function definition
P4.22 AO2 function definition
(reserve for 3004GB and below models)
P4.23 AO3 function definition
(reserve for 3004GB and below models)
P4.24 DO function definition
0: NULL
2: Output voltage (0 (0 ~ 10V / 0 ~ 20mA) maximum
voltage)
4: PID feedback (0 ~ 10V)
128
%
Min analog
value (V)
Figure. 5-4-1 Analog input linear curve
analog value Input %
P4.07
P4.02 P4.04
P4.01
P4.03
P4.06
Figure. 5-4-2 Analog input non-linear curve
Max analog
value (V)
P4.14
P4.12
P4.09
A nalog
P4.08
P4.11
P4.13
Setting range: 0~14 [0]
Setting range: 0~14 [0]
Setting range: 0~14 [0]
Setting range: 0~14 [0]
1: Output current (0-2IN)
3: PID setting (0 ~ 10V)
5: Calibration signal (5V )
input