P2.04 Frequency lower limit deal mode
0: Run at Frequency lower limit
2: Stopping
Notes:
If setting is 0, when the reference frequency is lower than frequency lower limit, the inverter will run at
frequency lower limit instead of reference frequency. As shown in Figure. 5-2-3.
Option 1: When the inverter runs at 0 frequency, if the set frequency is less than the lower limit frequency, the
inverter should run at the lower limit frequency, and run at 0 frequency after the delay time arrives at P3.30,
as shown in Fig. 5-2-4.
Sleep function is enabled and the inverter is in sleep running, then no matter P2.04 is 0 or 1, the inverter
should be regarded as running at 0 frequency.
Option 3: Reserve
105
Operation Freq.(Hz)
Figure. 5-2-2 FWD/REV switching time
Setting range: 0~3 [0]
1: Run at zero-speed.
3: Zero speed operation
Operation Freq.(Hz)
Reference
Frequency 1
Lower limit
Frequency
Reference
Frequency 2
Figure. 5-2-3 Running at Frequency lower limit
Operation Freq.(Hz)
Frequency lower limit arrived delay time (P3.30)
Reference
Freq. 1
Frequency
lower limit
Reference
Freq. 2
Figure. 5-2-4 Zero-speed running
Chapter 5 Detailed Function Introductions
t1
Frequency lower limit arrivied delay time(P3.22)
Time
Time
Time