Alpha 6000S series User Manual page 18

Table of Contents

Advertisement

Catego
Terminal
ry
label
Multi-function input
X1
terminal 1
Multi-function input
X2
terminal 2
Multi-function input
X3
terminal 3
Multi-function input
X4
terminal 4
Multi-function input
X5
terminal 5
Multi-function input
X6
terminal 6
Multi-function input
X7
terminal 7
Multi-function input
X8
terminal 8
Multi-function input
X9
terminal 9
Multi-function input
X10
terminal 10
Open collector output
DO
terminal
Y1
Open collector output
17
Description of terminal
Name
It can be defined as a
multi-function on-off input
terminal through
programming, please see
Section 5.4 of Chapter V
Function Description of Input
Terminals of I/O Terminal
Control (Group P3) for
details.
X3 can be used as an ordinary
multi-function terminal for
S2R4GB ~ 3004GB series
inverters, it can also be
programmable and used as an
input port of high speed
pulse; but it can only be used
as an ordinary multi-function
terminal for 35R5GB ~
3500G series inverters.
It can be defined as an input
port of high-speed pulse
through programming, please
see Section 5.4 of Chapter V
Function Description of Input
Terminals of I/O Terminal
Control (Group P3) for
details.
X6 is exclusive for 35R5GB
and above models.
It can be defined as a
multi-function on-off input
terminal through
programming, please see
Section 5.4 of Chapter V
Function Description of Input
Terminals of I/O Terminal
Control (Group P3) for
details.
X7 ~ X10, located on IO
extension board, are
extension terminals,
and are exclusive for
35R5GB and above models.
It can be defined as a
multi-function output
terminal for pulse signal
through programming. It can
also be used as an on-off
output terminal. Section 5.4
of Chapter V Function
Description of Output
Terminals of I/O Terminal
Control (Group P3).
It can be defined as a
Chapter 2 Installation and Wiring
function
Opto-coupler isolation input
Input impedance R = 3.9kΩ
Maximum input frequency:
Input voltage range: 0~30V
Common port: PLC
Reference ground: COM
24V
PLC
X1-X6
COM
Opto-coupler isolation input
Input impedance R = 3.9kΩ
Maximum input frequency: 400Hz
Input voltage range: 0~30V
Common port: PLC1
Reference ground: COM1
24V
PLC1
X7-X10
COM1
Opto-coupler isolated open collector
output.
Range of operating voltage: 0V~26V
Maximum output current: 50mA
Range of Output frequency: 0~50KHz
Reference ground: COM
Opto-coupler isolated open collector
Specification
200Hz (ordinary IO)
50KHz (high-speed pulse)
+24V
+5V
R
+24V
+5V
R