4. Cut off the power supply and wait until keypad display disappears completely.
5. Switch on the power supply again.
6. Conduct the communication with PLC.
Setting of Communication Parameters
To communicate with PLC, communication-related parameters should be set. In the following table, only Pb.01 (ID
Number) and Pb.04 (response delay time) can be revised during operation to facilitate debugging, which becomes
effective immediately, while the rest parameters cannot be revised during operation. Then can only be set during the
stop time, and the reset parameters will not become effective until the inverter is powered off and then restarted.
"○" revisable during operation;"×" non-revisable during operation
Function
Name of
Code
Parameter
Frequency
P0.03
Setting
Source 1
Frequency
P0.04
Setting
Source 2
Operation
Command
P0.07
Giving
Manner
Setting
Upper limit
P0.11
of frequency
source
199
Setting Range
0: NULL
1: Frequency number setting,
number knob adjustment
2: Terminal AI1
3: Terminal AI2
4: Terminal AI3 (Reserved for
3004GB and the below)
5: Impulse input
6: Communication giving
7: Linear speed (Reserved)
8: Multi-segment speed
9: Terminal UP/DOWN
10: (PLC)Program-timing
operation (PLC)
11: PID
12: Pendulum frequency
operation (and other special
operation modes)
When the frequency source is
0~7, if the multi-segment speed
terminal is effective, treat it as
"multi-segment speed"
0~8: the same as above
9: torque difference
compensation
0: Keypad control
1: Terminal control 1(Key STOP
ineffective)
2: Terminal control 2(Key STOP
effective )
3: Serial communication 1(Key
STOP ineffective)
4: Serial communication 2(Key
STOP effective)
5: Terminal control 3(Key STOP
& JOG ineffective)
0: Digital setting
1: Terminal AI1
2: Terminal AI2
3: Terminal AI3 (Reserved for
3004GB and the below)
4: Impulse input
5: Communication setting
Appendix 4 Use of MODBUS Communication
Ex-factory
Setting
1
0
0
0
After the
communication function
Revision
is selected, MODBUS
can be written into the
register
0002H
×
0005H
×
0001H
0008H
×