Alpha 6000S series User Manual page 170

Table of Contents

Advertisement

Fault
Name of Protection
Display
Overcurrent with the
OC3
constant-speed operation
Overvoltage with the accelerated
Ou1
operation
Overvoltage with the decelerated
Ou2
operation
Overvoltage with the
Ou3
constant-speed operation
GF
Output earthing
OH1
Heat radiator overheating
169
Possible Cause to Fault
Abnormal load
The acceleration or
deceleration time is set to
be too short
The power voltage is low
The frequency inverter
power is too small
The frequency inverter
output load is
short-circuited
The input voltage is
abnormal
The acceleration time set is
too short
The stalling overvoltage
point is too low
The input voltage is
abnormal
The deceleration time is too
short
The load inertia torque is
large
The stalling overvoltage
point is too low
The input voltage is
abnormal
The acceleration or
deceleration time is too
short
The load inertia torque is
large
The stalling overvoltage
point is too low
The output earthing current
exceeds the specified value
The environment
temperature is too high
The air duct is blocked
The fan works abnormally/
is damaged
Chapter 6 Troubleshooting
Countermeasure
insulation
Check the load
Increase the acceleration
or deceleration time
appropriately
Check the input power
supply
Select the
frequency-inverter with
the larger power
Check the motor coil
resistance and the motor
insulation
Check the input power
supply; check & test the
electrical level setting
Increase the acceleration
time appropriately
Raise the stalling
overvoltage point
Check the input power
supply; check & test the
electrical level setting
Increase the deceleration
time appropriately
Add the appropriate
brake components
additionally
Raise the stalling
overvoltage point
Check the input power
supply; check & test the
electrical level setting
Increase the deceleration
time appropriately
Add the appropriate
brake components
additionally
Raise the stalling
overvoltage point
Check whether the motor
insulation has become
poor
Check whether the
connection line between
the frequency inverter
and the motor is damaged
Reduce the environment
temperature
Clear the air duct
Replace the fan

Advertisement

Table of Contents
loading

This manual is also suitable for:

6000v series6700s series

Table of Contents