Appendix 4 Use of MODBUS Communication
[08H]
Loop Test Command: the command content is fed back originally in the form of response and is used for test of
signal transmission and returning between the main controller and the frequency inverter. Arbitrary values can be
used as the test code and data.
Example: loop feedback test
Command Content
Frequency Inverter
Address
Command Code
Test Code
Test Data
CRC
[10H]
Single-character Writing Command: write the content into the specified register, and write the specified data in the
specified register. The data saved should be among the order of record codes. The command content should be
arrayed in the sequence of high 8 bits and low 8 bits.
Example: set the frequency as 50.0Hz
Command Content
Frequency Inverter
Address
Command Code
Start
Address
Number of
Addresses
Number of Data
Content of
Data
CRC
[10H]
Data Saving Command: write the MODBUS register address corresponding to the function parameters into the
special saving address of 0xFF, and save the parameter content into EEPROM. It is equivalent to ENTER of the
keypad to save the data without being lost. The command content is arrayed in the order of high 8 bits and low 8 bits.
00FFH is specially used for data saving and is effective when Pb.06=0.
Example: set the frequency as 30.0Hz and save it in EEPROM.
204
Normal Response Content
Frequency Inverter
01
08
Command Code
High Bit
00
Test
Code
Low Bit
00
High Bit
12
Test
Data
Low Bit
34
High Bit
ED
CRC
Low Bit
7C
Normal Response Content
Frequency Inverter
01
Command Code
10
High Bit
00
Start
Address
Low Bit
02
High Bit
00
Number
of
Low Bit
01
Addresses
02
High Bit
13
CRC
Low Bit
88
High Bit AA
Low Bit
E4
Notes: The number of data doubles that of address.
01
Address
08
High Bit
00
Low Bit
00
High Bit
12
Low Bit
34
High Bit
ED
Low Bit
7C
01
Address
10
High Bit
00
Low Bit
02
High Bit
00
Low Bit
01
High Bit
A0
Low Bit
90
Abnormal Response Content
Frequency
01
Inverter Address
Command Code
88
Abnormality
03
Code
High Bit
06
CRC
Low Bit
01
Abnormal Response Content
Frequency
01
Inverter Address
Command Code
90
Abnormality
03
Code
High Bit
0C
CRC
Low Bit
01